4906-9211 SIMPLEX, AMBER/CLEAR WHITE WALL MT VO.
4906-9211 Simplex, Multi-Candela TrueAlert addressable combination strobes are individually addressed and individually controlled with power, supervision, and control supplied from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs). A single assembly provides an amber lens strobe for non-fire alarm, alert notification for use with Emergency Communications Systems, and a clear lens strobe for fire alarm notification.
Individually addressed and separately controlled multi-candela V/O (visible only) notification appliance with one amber ALERT strobe and one clear lens FIRE strobe provides:
- Combination unit allows mounting two visible notification appliances at the same installation site.
- Multi-candela xenon strobes with synchronized 1 Hz flash rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, or 110 cd.
- Advanced addressable notification controlled by IDNAC SLCs from Simplex® 4100ES fire alarm control panels with EPS/EPS+ power supplies (and 4009 IDNAC Repeaters) providing regulated 29 VRMS allowing strobes to operate with lower current even under battery backup.
- Amber lens with “ALERT” lettering produces a signal unique from clear lens fire alarm evacuation strobes for use with Emergency Communications Systems.
- Clear lens with “FIRE” lettering provides visible notification for fire alarm conditions.
- Both strobes connect on same SLC, are separately addressed, and provide independent operation; (Operation is clear/Fire OR amber/Alert, not both).
- Wiring supervision to each strobe allowing “T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring).
- TrueAlert Device Reports at the control panel detailing appliance point ID, custom label, type, and candela setting.
- Magnet test diagnostics to assist checkout and testing of appliances and wiring.
- Compatibility with ADA requirements.
- Compatibility with legacy TrueAlert addressable systems for upgrade and replacement .
- Clear lens strobe is UL listed to Standard 1971, ULC listed to Standard S526.
- Amber lens strobe is UL listed to Standard 1638 (due to non-white lens); and provides light dispersion patterns of UL Standard 1971; ULC listing is to Standard S526.
LED indicator and magnet test feature:
- Each appliance LED can be selected to display each polling cycle to indicate appliance supervision.
- In diagnostic mode, the magnet test pulses the LED to indicate appliance address AND pulses to indicate the intensity selection; a brief output of the strobe is also selectable to confirm operation.