4009-9401 SIMPLEX, 4009 TRUEALERT ADDR CONTROLLER.
4009-9401 Simplex, TrueAlert Addressable Operation Features Each individually addressed notification appliance receives power and control over a single wire pair providing:
- Supervised wiring connections to each appliance that support using “T-tapped” wiring for Class B circuits (Class A circuits require in/out wiring).
- Horns sounding with selectable high or low output, as Temporal 3 or March Time pattern (60 or 120 bpm), or Steady On, controlled separately from visible appliances on the same two-wire circuit.
- Visible appliances operating synchronized at 1 Hz.
- Control over power limited, isolated output Signaling Line Circuits (SLCs) with up to 63 addressable appliances per SLC, and up to 189 appliances per control source.
- Control sources selectable to provide individual appliance magnetic test mode and appliance LED polling indicator.
- 4100ES, 4100U and 4010ES systems also provide additional control capabilities using Virtual NAC (VNAC) appliance groupings across SLCs and across control sources.
Class B, “T-tapped” wiring advantages:
- Less wiring distance is required since traditional end-of-line Class B wiring supervision is not needed.
- With less wiring distance required, voltage drops can be reduced, allowing more appliances per wire run.
Extensive internal diagnostics include:
- LED status indicators that identify channel and trouble.
- Support for host fire alarm control panel WALK TEST system test with IDNet or RUI communications.
- Status monitoring of battery, input power, and earth faults.
Optional internal modules:
- Class A Three Channel Adapter Module.
- IDNet Communications: Repeater or Fiber Optic Receiver/Repeater; models for Class A or Class B.