2190-9160 Simplex, Signal ZAMs supervise and operate 24 VDC notification appliances, speakers, and telephone circuits. Output capacity is up to 2 A @ 24 VDC, or 50 W of 25 VRMS speakers, or up to three simultaneously activated firefighter phones. The signal ZAM is available for either Style Y/Class B or Style Z/Class A operation for notification appliance circuits.
Compatible with the following Simplex® fire alarm control panels when equipped with MAPNET II communications:
MAPNET II communications can be wired:
MAPNET II zone adapter modules (ZAMs) provide an addressable interface between conventional zone devices and the host fire alarm control panel.
General Specifications
Communications: Supplied by MAPNET II, 24 to 40 VDC with data.
Power: Separate 24 VDC required from listed fire alarm power supply.
Wire Connections: Screw terminals for in/out wiring, 18 to 12 AWG wire.
Temperature Range: 32° F to 120° F (0° C to 49° C) intended for indoor operation.